v2.0 — 2026-05-22

A new rack software version is available. Changes versus v1:

75 kWh rack

  • Stability fixes — increase operational uptime.
  • Lower self-consumption — to reduce operational energy cost, the rack now drops into InvSt = 7 (Standby) whenever the EMS writes WSet = 0 (4030140302). Writing any non-zero WSet (e.g. 5 000 W) returns it to Running immediately. The state transition is driven entirely by the value of WSet — no separate state command from the EMS. See Integration guide → Control flow.
  • Rack fault reset over Modbus — EMS can now clear active rack errors by writing 1 to register 40427 per rack. The register self-clears to 0 once the reset has been applied. See Integration guide → Resetting rack faults.
  • Total battery DC voltage exposed — Model 802 now publishes V (total battery DC voltage) at register 40441. See Integration guide → Model 802.