Release notes
This page tracks documentation changes between versions of the C-Battery Technical Wiki. For the current docs see v2.0. Older versions remain accessible via the version switcher.
v2.0 — 2026-05-22
A new rack software version is available. Changes versus v1:
75 kWh rack
- Stability fixes — increase operational uptime.
- Lower self-consumption — to reduce operational energy cost, the rack now drops into
InvSt = 7(Standby) whenever the EMS writesWSet = 0(40301–40302). Writing any non-zeroWSet(e.g.5 000 W) returns it to Running immediately. The state transition is driven entirely by the value ofWSet— no separate state command from the EMS. See Integration guide → Control flow. - Rack fault reset over Modbus — EMS can now clear active rack errors by writing
1to register40427per rack. The register self-clears to0once the reset has been applied. See Integration guide → Resetting rack faults. - Total battery DC voltage exposed — Model 802 now publishes
V(total battery DC voltage) at register40441. See Integration guide → Model 802.
v1 — initial release
First published version of the wiki, covering:
- 75 kWh rack — integration guide and register reference.
- Other systems — integration guide and register reference for non-75 kWh deployments.