A CBEB1045 (C-Battery Energy Box) follows the EMS integration pages: the same points, addresses and start order. Its PCS is a stack of power modules and its battery has its own BMS, and that changes a few things.
Starting and stopping
Section titled “Starting and stopping”- Write
802_SetOp= 1 first. Until the battery is on the DC bus, it holds back704_WSetEna= 1 and802_SetInvState= 3, and applies them once it is. - The first start takes 8 to 15 s: the modules start in steps.
704_WSet= 0 stops the modules. The next setpoint starts them again, which takes about 8 s each time.- Write
704_WSet= 0 before802_SetOp= 2. The battery does not stop the modules before it leaves the DC bus.
Limits and state of charge
Section titled “Limits and state of charge”802_AChaMaxand802_ADisChaMaxare the BMS limit now.802_WChaRteMaxand802_WDisChaRteMaxcan read the PCS rating instead: take the battery limit from the current ×802_V, as in How it behaves.802_SoCis net: use all of 0–100 %. At 0 % discharging stops and the discharge limits read 0; at 100 % charging stops.
The battery protects itself
Section titled “The battery protects itself”701_W can differ from your setpoint, also while control is off:
- When cell voltages are too low, the battery can charge by itself.
- In a dangerous situation, it holds 0 W.
States and faults
Section titled “States and faults”701_InvSt |
Meaning |
|---|---|
| 0 | Control is off: 704_WSetEna = 0 or 802_SetInvState is not 3 |
| 7 | Control is on, 704_WSet is 0: the modules are stopped |
| 3 | Running |
| 6 | A module fault |
802_AlmRst does nothing on a CBEB1045. For a fault that stays, contact support@c-battery.technology.