Your EMS sets the power of a C-Battery BESS over Modbus TCP, with the standard SunSpec models. The BESS keeps itself safe: it caps every setpoint to its limits, and runs nothing during a fault.

These pages hold for every C-Battery BESS that follows SunSpec in full. The CBII75 legacy and the CBEB300 differ from SunSpec and have their own sections. The CBII75, the CBEB1045 and the CBEB3344 follow these pages, and their own sections say where they differ or add to them.

  • Connect and disconnect the battery, and start and stop it.
  • Set the active power, charging or discharging.
  • Read the state of charge, the energy and the power limits.
  • See whether it can run.
  • Reactive power or power factor control.
  • Grid forming: the BESS follows the grid.
Model SunSpec name You use it for
1 Common Identifying the device
701 DER AC Measurement Delivered power and PCS state
704 DER AC Controls Setting the power
713 DER Storage Capacity Energy
802 Battery Base Model Connecting, starting, limits and state of charge

Models 702, 714 and 715 are served as well, but you need nothing from them.

If your EMS follows the old wiki’s Other systems pages, check these:

  • Write 802_SetOp = 1, 802_SetInvState = 3 and 704_WSetEna = 1, then 704_WSet. Don’t wait for 701_InvSt = 3 in between: until there is a setpoint it can read 7.
  • 704_WSetEna = 0 ends control: the PCS stops converting, it does not keep running.
  • 802_SetInvState = 2 is not used: write 1 or 3.
  • Reset faults with 802_AlmRst. 715_AlarmReset does nothing.
  • Unit ID 1 does not answer: use 100 + the battery’s number.
  • 802_State takes SunSpec’s values: 5 is SOC protection, not float. See CBEB3344.
  • 713_SoC still holds the state of charge, the same as 802_SoC.