Overview
Your EMS sets the power of a C-Battery BESS over Modbus TCP, with the standard SunSpec models. The BESS keeps itself safe: it caps every setpoint to its limits, and runs nothing during a fault.
These pages hold for every C-Battery BESS that follows SunSpec in full. The CBII75 legacy and the CBEB300 differ from SunSpec and have their own sections. The CBII75, the CBEB1045 and the CBEB3344 follow these pages, and their own sections say where they differ or add to them.
What your EMS can do
Section titled “What your EMS can do”- Connect and disconnect the battery, and start and stop it.
- Set the active power, charging or discharging.
- Read the state of charge, the energy and the power limits.
- See whether it can run.
What it does not do
Section titled “What it does not do”- Reactive power or power factor control.
- Grid forming: the BESS follows the grid.
SunSpec models
Section titled “SunSpec models”| Model | SunSpec name | You use it for |
|---|---|---|
| 1 | Common | Identifying the device |
| 701 | DER AC Measurement | Delivered power and PCS state |
| 704 | DER AC Controls | Setting the power |
| 713 | DER Storage Capacity | Energy |
| 802 | Battery Base Model | Connecting, starting, limits and state of charge |
Models 702, 714 and 715 are served as well, but you need nothing from them.
Coming from the old wiki
Section titled “Coming from the old wiki”If your EMS follows the old wiki’s Other systems pages, check these:
- Write
802_SetOp= 1,802_SetInvState= 3 and704_WSetEna= 1, then704_WSet. Don’t wait for701_InvSt= 3 in between: until there is a setpoint it can read 7. 704_WSetEna= 0 ends control: the PCS stops converting, it does not keep running.802_SetInvState= 2 is not used: write 1 or 3.- Reset faults with
802_AlmRst.715_AlarmResetdoes nothing. - Unit ID 1 does not answer: use 100 + the battery’s number.
802_Statetakes SunSpec’s values: 5 is SOC protection, not float. See CBEB3344.713_SoCstill holds the state of charge, the same as802_SoC.