Fault reference

A PCS fault sets 701_InvSt = 6 and 802_State = 99. A fault clears by itself once its cause is gone. A latched fault needs 802_AlmRst = 1 after that: see Faults.

Every PCS fault sets bit 16, and the bit for its kind where SunSpec has one. 701_MnAlrmInfo names the active faults.

Bit SunSpec name Meaning
0 GROUND_FAULT Ground fault
1 DC_OVER_VOLT DC voltage too high
2 AC_DISCONNECT AC relay open
3 DC_DISCONNECT DC relay open
4 GRID_DISCONNECT Grid lost: islanding or a phase missing
6 MANUAL_SHUTDOWN Emergency stop
7 OVER_TEMP Over-temperature
8 OVER_FREQUENCY Grid frequency too high
9 UNDER_FREQUENCY Grid frequency too low
10 AC_OVER_VOLT Grid voltage too high
11 AC_UNDER_VOLT Grid voltage too low
12 BLOWN_STRING_FUSE Fuse blown
16 MANUFACTURER_ALRM Any PCS fault
Bit SunSpec name Meaning
0 COMMUNICATION_ERROR The PCS does not answer
25 OTHER_ALARM A PCS fault or a battery protection
26 OTHER_WARNING A PCS warning or a battery power reduction. It never stops the battery

A battery protection is not a PCS fault: it sets 802_AChaMax or 802_ADisChaMax of the direction it forbids to 0, and the PCS keeps running in the other direction.