Overview

The CBEB300 (C-Battery Energy Box) is a grid-forming battery container. It runs its own dispatch, driven by demand response: your EMS does not set its power. Over Modbus TCP your EMS turns the container on or off, and reads its state of charge, its DC power and its limits.

Modbus TCP to the container’s IP address, port 502, Unit ID 100 + the BESS number: 101 for the first. Unit ID 1 does not answer. Registers 40000 and 40001 read SunS.

To Point Address Value
Turn it on 704_WSetEna 40299 1
Turn it off, for example for maintenance 704_WSetEna 40299 0
  • Write it once: the container keeps it.
  • Where the cabinet’s on/off button is connected, it switches the same point, and the last one wins. Read 704_WSetEna back before you rely on it.
  • Do not write 704_WSet: the container sets its own power.
Point Address Meaning
713_SoC 40348 State of charge, in %
714_DCA 40358 Battery DC current, in A
714_DCW 40359 Battery DC power, in W. Positive discharges, negative charges
802_WChaRteMax 40411 The charge power it can take now, in W
802_WDisChaRteMax 40412 The discharge power it can give now, in W

802_WChaRteMax and 802_WDisChaRteMax change with the state of charge and the temperature. Read them as often as your EMS decides, and don’t keep them for long. The scaling of each point is in the Register reference.

SunSpec CBEB300
Power 704_WSet sets it The container sets its own power. 704_WSet is not used
704_WSetEna Enables the setpoint Turns the container on and off
802_WChaRteMax, 802_WDisChaRteMax The nameplate rate The limit right now

The map has the same layout and addresses as the CBII75 legacy: models 1, 701, 702, 704, 713, 714, 715 and 802, from 40002. You need 704, 713, 714 and 802. In your EMS, walk the map rather than using fixed addresses.