A CBEB1050 (C-Battery Energy Box) follows the EMS integration pages: the same points, addresses and start order. Its PCS is one cabinet and its battery racks have their own BMS, and that changes a few things.
Starting and stopping
Section titled “Starting and stopping”- Write
802_SetInvState= 3 and704_WSetEna= 1, then704_WSet. The PCS runs while both are on. 802_SetOpreads 1 after a restart: the battery is on the DC bus.704_WSet= 0 keeps the PCS running at 0 W:701_InvStreads 7, and the next setpoint applies without a new start.704_WSetEna= 0 or802_SetInvState= 1 stops the PCS.802_SetOp= 2 stops the PCS and keeps it stopped until you write 1. The battery racks stay connected;802_Statereads 1.
Limits and state of charge
Section titled “Limits and state of charge”802_WChaRteMaxand802_WDisChaRteMaxare the nameplate rate: the nominal power, the most the PCS and battery can ever charge or discharge. They are fixed for the installation.- The power it can charge or discharge right now is
802_AChaMaxor802_ADisChaMax×802_V. A battery protection sets the direction it forbids to 0. Read them every cycle and stay below both, as in How it behaves. - The battery never goes above either. It caps your setpoint to them, and it lowers the setpoint when the battery current goes above
802_AChaMaxor802_ADisChaMax: near the limit the PCS’s own losses can draw more from the battery than the AC power shows. So701_Wcan be lower than you asked. 802_SoCis net: use all of 0–100 %. At 0 % discharging stops and802_ADisChaMaxreads 0; at 100 % charging stops and802_AChaMaxreads 0.713_WHRtgis the usable energy,713_WHAvailthe energy available now.
States
Section titled “States”701_InvSt |
Meaning |
|---|---|
| 0 | The PCS is stopped |
| 2 | Starting |
| 3 | Running |
| 7 | Running at 0 W |
| 6 | A PCS fault, or the PCS does not answer |
802_State |
Name | Meaning |
|---|---|---|
| 1 | DISCONNECTED | Stopped by 802_SetOp = 2: write 1 |
| 3 | CONNECTED | Dispatch it |
| 99 | FAULT | It cannot run |
Faults
Section titled “Faults”At 701_InvSt = 6 or 802_State = 99, stop asking for power and show your operator 701_MnAlrmInfo: the active faults in words, for example AC bus under voltage; AC bus under frequency when the grid is gone.
- A fault clears by itself once its cause is gone, for example when the grid is back. The PCS then starts again if you still ask for power.
802_AlmRst= 1 resets the PCS’s latched faults once their cause is gone. It reads 0 again once done. One write per reset; never write it on a timer.
| Point | What it says |
|---|---|
701_Alrm |
Bit 16 MANUFACTURER_ALRM on every PCS fault, plus the SunSpec bit for the kind of fault where there is one |
701_MnAlrmInfo |
The active PCS faults; PCS not responding or PCS warning |
802_Evt1 |
Bit 0 COMMUNICATION_ERROR: the PCS does not answer. Bit 25 OTHER_ALARM: a PCS fault or a battery protection. Bit 26 OTHER_WARNING: a PCS warning or a battery power reduction |
A PCS warning or a battery power reduction never stops the battery. Every alarm and event bit: Fault reference. For a fault that stays, contact support@c-battery.technology.