A CBEB1050 (C-Battery Energy Box) follows the EMS integration pages: the same points, addresses and start order. Its PCS is one cabinet and its battery racks have their own BMS, and that changes a few things.

  • Write 802_SetInvState = 3 and 704_WSetEna = 1, then 704_WSet. The PCS runs while both are on.
  • 802_SetOp reads 1 after a restart: the battery is on the DC bus.
  • 704_WSet = 0 keeps the PCS running at 0 W: 701_InvSt reads 7, and the next setpoint applies without a new start.
  • 704_WSetEna = 0 or 802_SetInvState = 1 stops the PCS.
  • 802_SetOp = 2 stops the PCS and keeps it stopped until you write 1. The battery racks stay connected; 802_State reads 1.
  • 802_WChaRteMax and 802_WDisChaRteMax are the nameplate rate: the nominal power, the most the PCS and battery can ever charge or discharge. They are fixed for the installation.
  • The power it can charge or discharge right now is 802_AChaMax or 802_ADisChaMax × 802_V. A battery protection sets the direction it forbids to 0. Read them every cycle and stay below both, as in How it behaves.
  • The battery never goes above either. It caps your setpoint to them, and it lowers the setpoint when the battery current goes above 802_AChaMax or 802_ADisChaMax: near the limit the PCS’s own losses can draw more from the battery than the AC power shows. So 701_W can be lower than you asked.
  • 802_SoC is net: use all of 0–100 %. At 0 % discharging stops and 802_ADisChaMax reads 0; at 100 % charging stops and 802_AChaMax reads 0.
  • 713_WHRtg is the usable energy, 713_WHAvail the energy available now.
701_InvSt Meaning
0 The PCS is stopped
2 Starting
3 Running
7 Running at 0 W
6 A PCS fault, or the PCS does not answer
802_State Name Meaning
1 DISCONNECTED Stopped by 802_SetOp = 2: write 1
3 CONNECTED Dispatch it
99 FAULT It cannot run

At 701_InvSt = 6 or 802_State = 99, stop asking for power and show your operator 701_MnAlrmInfo: the active faults in words, for example AC bus under voltage; AC bus under frequency when the grid is gone.

  • A fault clears by itself once its cause is gone, for example when the grid is back. The PCS then starts again if you still ask for power.
  • 802_AlmRst = 1 resets the PCS’s latched faults once their cause is gone. It reads 0 again once done. One write per reset; never write it on a timer.
Point What it says
701_Alrm Bit 16 MANUFACTURER_ALRM on every PCS fault, plus the SunSpec bit for the kind of fault where there is one
701_MnAlrmInfo The active PCS faults; PCS not responding or PCS warning
802_Evt1 Bit 0 COMMUNICATION_ERROR: the PCS does not answer. Bit 25 OTHER_ALARM: a PCS fault or a battery protection. Bit 26 OTHER_WARNING: a PCS warning or a battery power reduction

A PCS warning or a battery power reduction never stops the battery. Every alarm and event bit: Fault reference. For a fault that stays, contact support@c-battery.technology.