Register reference

Addresses count from 0, with SunS at 40000. A value is the register times 10 to the power of its scale factor. Every name is the one in the SunSpec model.

Point SunSpec name Address Type Unit Access Notes
1_Mn Manufacturer 40004–40019 string – read C-Battery
1_Vr Version 40044–40051 string – read The software version
704_WSetEna Set Active Power Enable 40299 enum16 – read/write 1: the container is on. 0: off
713_SoC State of Charge 40348 uint16 %: register × 0.1 read
713_Pct_SF Percent Scale Factor 40352 sunssf – read −1
714_DCA DC Current 40358 int16 A: register × 0.1 read Battery DC current
714_DCW DC Power 40359 int16 W: register × 100 read Positive discharges, negative charges
714_DCA_SF DC Current Scale Factor 40368 sunssf – read −1
714_DCW_SF DC Power Scale Factor 40370 sunssf – read 2
802_WChaRteMax Nameplate Max Charge Rate 40411 uint16 W: register × 100 read The charge power it can take now, not the nameplate
802_WDisChaRteMax Nameplate Max Discharge Rate 40412 uint16 W: register × 100 read The discharge power it can give now, not the nameplate
802_WChaDisChaMax_SF Scale factor for maximum charge and discharge rate 40461 sunssf – read 2

Where each model starts today, to check your walk against.

Model SunSpec name Starts at
1 Common 40002
701 DER AC Measurement 40070
702 DER Capacity 40225
704 DER AC Controls 40277
713 DER Storage Capacity 40344
714 DER DC Measurement 40353
715 DERCtl 40398
802 Battery Base Model 40407
End – 40471