Register reference

A CBEB3344 serves these on top of the points in the Register reference, which has the addressing and the models.

Point SunSpec name Address Type Unit Access Notes
701_Alrm Alarm Bitfield 40076–40077 bitfield32 – read Why the PCS cannot run. Bits in the Fault reference
701_DERMode DER Operational Characteristics 40078–40079 bitfield32 – read 1 grid following, 2 grid forming
701_MnAlrmInfo Manufacturer Alarm Info 40193–40224 string – read Faults, then warnings, in words. ASCII, 64 characters
713_Sta Status 40350 enum16 – read Values below
715_DERHb DER Heartbeat 40401–40402 uint32 – read Ours
715_ControllerHb Controller Heartbeat 40403–40404 uint32 – read/write Yours
802_LocRemCtl Control Mode 40424 enum16 – read Values below
802_State State of the Battery Bank 40429 enum16 – read Can it run? Values below
802_Evt1 Battery Event 1 Bitfield 40433–40434 bitfield32 – read Pack faults and warnings. Bits in the Fault reference
802_EvtVnd1 Vendor Event Bitfield 1 40437–40438 bitfield32 – read Faults of this BESS. Bits in the Fault reference
802_EvtVnd2 Vendor Event Bitfield 2 40439–40440 bitfield32 – read Warnings of this BESS. Bits in the Fault reference

Every value SunSpec defines for each point that takes one of a list.

Value SunSpec name Meaning
0 OK No fault, no warning
1 WARNING A warning: it keeps running
2 ERROR A fault: it cannot run
Value SunSpec name Meaning
0 REMOTE Always: your EMS controls it
1 LOCAL Not used
Value SunSpec name Meaning
1 DISCONNECTED Off the DC bus: write 802_SetOp = 1
2 INITIALIZING Not used
3 CONNECTED On the DC bus: dispatch it
4 STANDBY Not used
5 SOC PROTECTION At a state of charge limit
6 SUSPENDING Not used
99 FAULT It cannot run: the Fault reference says why
Type Registers Holds
uint32 2 Unsigned 32-bit integer, high register first
enum16 1 One of the values listed for the point
bitfield32 2 32 bits, high register first. Each bit stands on its own
string – ASCII, two characters per register, padded with 0