Fault reference

When a CBEB3344 cannot run, 802_State reads 99 and the bits on this page say why. They are in four registers:

  • 802_EvtVnd1: faults of this BESS, such as an emergency stop or gas.
  • 802_EvtVnd2: warnings of this BESS. A warning never stops the battery.
  • 701_Alrm: faults of the PCS.
  • 802_Evt1: faults and warnings of the battery.

Who acts says what has to happen before it runs again:

Who acts Meaning
by itself Nothing: it runs again once the cause is gone
802_AlmRst Write 1 to 802_AlmRst once the cause is gone
on site Someone has to go to the battery
Bit Fault Who acts Notes
0 Emergency stop on site Includes the EPO
1 Fire detected on site
2 Hydrogen safety relay open on site Opens at 10 %LEL
3 BCU relay open on site The BCU’s own safety relay
4 Main safety relay open on site
5 Safety chain not energised on site All five safety relays open
6 Hydrogen at 10 %LEL by itself Or the gas detector’s relay, which trips at 10 %LEL
7 Hydrogen at 20 %LEL by itself
8 BCU, gas detector or PCS not answering by itself For 60 s
9 Physical intervention required – Set with any fault reset on site, also one of the PCS
10 EMS heartbeat lost by itself Only where the heartbeat check is on
11 Control fuse blown on site The 24 V control fuse
12 Fire suppression fault on site
13 Surge arrester failed on site
14 Hydrogen at 5 %LEL by itself Held at 0 W before any relay opens
Bit Warning Notes
0 Air too hot (dehumidifier)
1 Air too humid (dehumidifier)
2 Coolant low (chiller)
3 Heater failure (chiller)
4 Humidity out of range (gas detector) Outside 40–60 %RH
5 Temperature out of range (gas detector) Below 5 or above 60 °C
Bit SunSpec name Who acts
0 GROUND_FAULT on site
1 DC_OVER_VOLT 802_AlmRst
2 AC_DISCONNECT on site
3 DC_DISCONNECT on site
4 GRID_DISCONNECT 802_AlmRst
6 MANUAL_SHUTDOWN on site
7 OVER_TEMP 802_AlmRst
8 OVER_FREQUENCY 802_AlmRst
9 UNDER_FREQUENCY 802_AlmRst
10 AC_OVER_VOLT 802_AlmRst
11 AC_UNDER_VOLT 802_AlmRst
12 BLOWN_STRING_FUSE on site
14 MEMORY_LOSS on site
16 MANUFACTURER_ALRM see 802_EvtVnd1 if set, else 802_AlmRst

Any other PCS fault sets MANUFACTURER_ALRM: 701_MnAlrmInfo names it. A PCS fault that needs someone on site also sets 802_EvtVnd1 bit 9.

Condition Fault bit Warning bit
COMMUNICATION_ERROR 0 –
OVER_TEMP 1 2
UNDER_TEMP 3 4
OVER_CHARGE_CURRENT 5 6
OVER_DISCHARGE_CURRENT 7 8
OVER_VOLT 9 10
UNDER_VOLT 11 12
UNDER_SOC_MIN 13 14
OVER_SOC_MAX 15 16
VOLTAGE_IMBALANCE – 17
TEMPERATURE_IMBALANCE 18 19
GROUND_FAULT 22 –
OTHER 25 26

They clear by themselves. 25 and 26 also flag 802_EvtVnd1 and 802_EvtVnd2.