When a CBEB3344 cannot run, 802_State reads 99 and the bits on this page say why. They are in four registers:
802_EvtVnd1: faults of this BESS, such as an emergency stop or gas.
802_EvtVnd2: warnings of this BESS. A warning never stops the battery.
701_Alrm: faults of the PCS.
802_Evt1: faults and warnings of the battery.
Who acts says what has to happen before it runs again:
| Who acts |
Meaning |
| by itself |
Nothing: it runs again once the cause is gone |
| 802_AlmRst |
Write 1 to 802_AlmRst once the cause is gone |
| on site |
Someone has to go to the battery |
| Bit |
Fault |
Who acts |
Notes |
| 0 |
Emergency stop |
on site |
Includes the EPO |
| 1 |
Fire detected |
on site |
|
| 2 |
Hydrogen safety relay open |
on site |
Opens at 10 %LEL |
| 3 |
BCU relay open |
on site |
The BCU’s own safety relay |
| 4 |
Main safety relay open |
on site |
|
| 5 |
Safety chain not energised |
on site |
All five safety relays open |
| 6 |
Hydrogen at 10 %LEL |
by itself |
Or the gas detector’s relay, which trips at 10 %LEL |
| 7 |
Hydrogen at 20 %LEL |
by itself |
|
| 8 |
BCU, gas detector or PCS not answering |
by itself |
For 60 s |
| 9 |
Physical intervention required |
– |
Set with any fault reset on site, also one of the PCS |
| 10 |
EMS heartbeat lost |
by itself |
Only where the heartbeat check is on |
| 11 |
Control fuse blown |
on site |
The 24 V control fuse |
| 12 |
Fire suppression fault |
on site |
|
| 13 |
Surge arrester failed |
on site |
|
| 14 |
Hydrogen at 5 %LEL |
by itself |
Held at 0 W before any relay opens |
| Bit |
Warning |
Notes |
| 0 |
Air too hot (dehumidifier) |
|
| 1 |
Air too humid (dehumidifier) |
|
| 2 |
Coolant low (chiller) |
|
| 3 |
Heater failure (chiller) |
|
| 4 |
Humidity out of range (gas detector) |
Outside 40–60 %RH |
| 5 |
Temperature out of range (gas detector) |
Below 5 or above 60 °C |
| Bit |
SunSpec name |
Who acts |
| 0 |
GROUND_FAULT |
on site |
| 1 |
DC_OVER_VOLT |
802_AlmRst |
| 2 |
AC_DISCONNECT |
on site |
| 3 |
DC_DISCONNECT |
on site |
| 4 |
GRID_DISCONNECT |
802_AlmRst |
| 6 |
MANUAL_SHUTDOWN |
on site |
| 7 |
OVER_TEMP |
802_AlmRst |
| 8 |
OVER_FREQUENCY |
802_AlmRst |
| 9 |
UNDER_FREQUENCY |
802_AlmRst |
| 10 |
AC_OVER_VOLT |
802_AlmRst |
| 11 |
AC_UNDER_VOLT |
802_AlmRst |
| 12 |
BLOWN_STRING_FUSE |
on site |
| 14 |
MEMORY_LOSS |
on site |
| 16 |
MANUFACTURER_ALRM |
see 802_EvtVnd1 if set, else 802_AlmRst |
Any other PCS fault sets MANUFACTURER_ALRM: 701_MnAlrmInfo names it. A PCS fault that needs someone on site also sets 802_EvtVnd1 bit 9.
| Condition |
Fault bit |
Warning bit |
| COMMUNICATION_ERROR |
0 |
– |
| OVER_TEMP |
1 |
2 |
| UNDER_TEMP |
3 |
4 |
| OVER_CHARGE_CURRENT |
5 |
6 |
| OVER_DISCHARGE_CURRENT |
7 |
8 |
| OVER_VOLT |
9 |
10 |
| UNDER_VOLT |
11 |
12 |
| UNDER_SOC_MIN |
13 |
14 |
| OVER_SOC_MAX |
15 |
16 |
| VOLTAGE_IMBALANCE |
– |
17 |
| TEMPERATURE_IMBALANCE |
18 |
19 |
| GROUND_FAULT |
22 |
– |
| OTHER |
25 |
26 |
They clear by themselves. 25 and 26 also flag 802_EvtVnd1 and 802_EvtVnd2.