Register reference

Addresses count from 0, with SunS at 40000. A value is the register times 10 to the power of its scale factor. Every name is the one in the SunSpec model. The addresses come from a rack (Unit ID 101) on software 2.0.

Point SunSpec name Address Type Unit Access Notes
1_Mn Manufacturer 40004–40019 string – read C-Battery
1_Vr Version 40044–40051 string – read The rack’s software version, such as 2.0.0
1_DA Device Address 40068 uint16 – read Modbus device address
701_InvSt Inverter State 40074 enum16 – read 3 running, 7 standby, 6 fault
701_W Active Power 40080 int16 W: register × 100 read Positive: discharging
701_PF Power Factor 40083 int16 register × 0.001 read
701_Hz Frequency 40087–40088 uint32 Hz: register × 0.001 read
701_AL1 Amps L1 40115 int16 A: register × 0.1 read
701_VL1L2 Phase Voltage L1-L2 40116 uint16 V: register × 0.1 read
701_AL2 Amps L2 40138 int16 A: register × 0.1 read
701_VL2L3 Phase Voltage L2-L3 40139 uint16 V: register × 0.1 read
701_AL3 Amps L3 40161 int16 A: register × 0.1 read
701_VL3L1 Phase Voltage L3-L1 40162 uint16 V: register × 0.1 read
701_A_SF Current Scale Factor 40183 sunssf – read −1
701_V_SF Voltage Scale Factor 40184 sunssf – read −1
701_Hz_SF Frequency Scale Factor 40185 sunssf – read −3
701_W_SF Active Power Scale Factor 40186 sunssf – read 2
701_PF_SF Power Factor Scale Factor 40187 sunssf – read −3
701_VA_SF Apparent Power Scale Factor 40188 sunssf – read 2
701_Var_SF Reactive Power Scale Factor 40189 sunssf – read 2
704_WSetEna Set Active Power Enable 40299 enum16 – read/write 1: the rack follows 704_WSet. 0: standby
704_WSetMod Set Active Power Mode 40300 enum16 – read/write Fixed at 1, watts. Don’t write it
704_WSet Active Power Setpoint (W) 40301–40302 int32 W: register × 100 read/write Positive discharges, negative charges. Below 500 W either way: standby
704_WSet_SF Active Power Scale Factor 40332 sunssf – read 2
713_WHRtg Energy Rating 40346 uint16 Wh: register × 100 read
713_WHAvail Energy Available 40347 uint16 Wh: register × 100 read
713_SoC State of Charge 40348 uint16 %: register × 0.1 read
713_SoH State of Health 40349 uint16 %: register × 0.1 read
713_WH_SF Energy Scale Factor 40351 sunssf – read 2
713_Pct_SF Percent Scale Factor 40352 sunssf – read −1
714_NPrt Number Of Ports 40357 uint16 – read 1
714_DCA DC Current 40358 int16 A: register × 0.1 read
714_DCW DC Power 40359 int16 W: register × 100 read
714_DCA_SF DC Current Scale Factor 40368 sunssf – read −1
714_DCV_SF DC Voltage Scale Factor 40369 sunssf – read −1
714_DCW_SF DC Power Scale Factor 40370 sunssf – read 2
802_WChaRteMax Nameplate Max Charge Rate 40411 uint16 W: register × 100 read The charge limit now, not the nameplate
802_WDisChaRteMax Nameplate Max Discharge Rate 40412 uint16 W: register × 100 read The discharge limit now, not the nameplate
802_AlmRst Alarm Reset 40427 uint16 – read/write Write 1 to reset a fault. Reads 0 again once applied
802_V External Battery Voltage 40441 uint16 V read Battery DC voltage. From software 3.0 scaled by 802_V_SF at 40466
802_AChaMax Max Charge Current 40452 uint16 A: register × 0.1 read The charge limit now
802_ADisChaMax Max Discharge Current 40453 uint16 A: register × 0.1 read The discharge limit now
802_WChaDisChaMax_SF Scale factor for maximum charge and discharge rate 40461 sunssf – read 2
802_AMax_SF Scale factor for instantaneous DC charge/discharge current 40469 sunssf – read −1

From software 3.0 the map holds more points of these models, among them 802_SetOp, 802_SetInvState, 802_State and 802_SoC. They are not part of the rack’s control: start and stop it with 704_WSetEna.

Where each model starts today, to check your walk against.

Model SunSpec name Starts at
1 Common 40002
701 DER AC Measurement 40070
702 DER Capacity 40225
704 DER AC Controls 40277
713 DER Storage Capacity 40344
714 DER DC Measurement 40353
715 DERCtl 40398
802 Battery Base Model 40407
End – 40471