How it behaves

  • 704_WSetEna = 1: the rack follows 704_WSet. 0: it ignores 704_WSet and goes to standby. The rack keeps the value, so write it once after commissioning. Write 0 to hand control back to the rack, for example for maintenance.
  • 704_WSet = 0 puts the rack in standby, any other value runs it. A setpoint below 500 W either way counts as 0.
  • 704_WSet holds W / 100, so the setpoint moves in steps of 100 W. Positive discharges, negative charges.
  • 704_WSetMod is fixed at 1 (watts). You don’t write it.
  • 802_SetOp and 802_SetInvState are in the map from software 3.0, but the rack ignores them.
flowchart LR
    S["Standby<br/>701_InvSt = 7"]
    R["Running<br/>701_InvSt = 3"]
    F["Fault<br/>701_InvSt = 6"]
    S -- "704_WSetEna = 1<br/>and 704_WSet ≠ 0" --> R
    R -- "704_WSet = 0<br/>or 704_WSetEna = 0" --> S
    R -. "fault" .-> F
    S -. "fault" .-> F
    F -- "802_AlmRst = 1, with<br/>704_WSetEna = 1 and 704_WSet ≠ 0" --> R
  • 802_WChaRteMax and 802_WDisChaRteMax are the charge and discharge limits right now, in W. 802_AChaMax and 802_ADisChaMax give the same in A.
  • Read them every cycle: they change with the state of charge and the temperature.
  • A setpoint above the limit is cut to it, so 701_W can be lower than you asked.
701_InvSt Name Meaning
3 RUNNING Follows 704_WSet
7 STANDBY 704_WSet is 0, or 704_WSetEna is 0. Low self-consumption
6 FAULT It cannot run: see Resetting a fault
0, 1, 2 OFF, SLEEPING, STARTING On its way: with 704_WSetEna = 1 and a setpoint, it runs by itself
4, 5 THROTTLED, SHUTTING_DOWN Not used on this rack

Each rack has its own Unit ID: 100 + its number, so 101 for rack 1, 102 for rack 2. Write each rack on its own: there is no total for the site and no reset for all racks at once.

When 701_InvSt reads 6 and the cause is gone, write 802_AlmRst = 1 to that rack. It reads 1 until the rack has applied the reset, then 0. The rack then leaves the fault and, with 704_WSetEna = 1 and a setpoint, runs again. No power cycle is needed. The inverter can wait up to about 15 minutes in 701_InvSt = 1 before it runs.

1_Vr holds the rack’s software version. Standby, 802_V and 802_AlmRst need version 2.0 or later. Before 2.0 the rack kept running at 0 W instead of going to standby, and a fault needed a power cycle or a visit.