How it behaves
Control
Section titled “Control”704_WSetEna= 1: the rack follows704_WSet. 0: it ignores704_WSetand goes to standby. The rack keeps the value, so write it once after commissioning. Write 0 to hand control back to the rack, for example for maintenance.704_WSet= 0 puts the rack in standby, any other value runs it. A setpoint below 500 W either way counts as 0.704_WSetholds W / 100, so the setpoint moves in steps of 100 W. Positive discharges, negative charges.704_WSetModis fixed at 1 (watts). You don’t write it.802_SetOpand802_SetInvStateare in the map from software 3.0, but the rack ignores them.
flowchart LR
S["Standby<br/>701_InvSt = 7"]
R["Running<br/>701_InvSt = 3"]
F["Fault<br/>701_InvSt = 6"]
S -- "704_WSetEna = 1<br/>and 704_WSet ≠ 0" --> R
R -- "704_WSet = 0<br/>or 704_WSetEna = 0" --> S
R -. "fault" .-> F
S -. "fault" .-> F
F -- "802_AlmRst = 1, with<br/>704_WSetEna = 1 and 704_WSet ≠ 0" --> R
Limits
Section titled “Limits”802_WChaRteMaxand802_WDisChaRteMaxare the charge and discharge limits right now, in W.802_AChaMaxand802_ADisChaMaxgive the same in A.- Read them every cycle: they change with the state of charge and the temperature.
- A setpoint above the limit is cut to it, so
701_Wcan be lower than you asked.
States
Section titled “States”701_InvSt |
Name | Meaning |
|---|---|---|
| 3 | RUNNING | Follows 704_WSet |
| 7 | STANDBY | 704_WSet is 0, or 704_WSetEna is 0. Low self-consumption |
| 6 | FAULT | It cannot run: see Resetting a fault |
| 0, 1, 2 | OFF, SLEEPING, STARTING | On its way: with 704_WSetEna = 1 and a setpoint, it runs by itself |
| 4, 5 | THROTTLED, SHUTTING_DOWN | Not used on this rack |
Several racks
Section titled “Several racks”Each rack has its own Unit ID: 100 + its number, so 101 for rack 1, 102 for rack 2. Write each rack on its own: there is no total for the site and no reset for all racks at once.
Resetting a fault
Section titled “Resetting a fault”When 701_InvSt reads 6 and the cause is gone, write 802_AlmRst = 1 to that rack. It reads 1 until the rack has applied the reset, then 0. The rack then leaves the fault and, with 704_WSetEna = 1 and a setpoint, runs again. No power cycle is needed. The inverter can wait up to about 15 minutes in 701_InvSt = 1 before it runs.
Software versions
Section titled “Software versions”1_Vr holds the rack’s software version. Standby, 802_V and 802_AlmRst need version 2.0 or later. Before 2.0 the rack kept running at 0 W instead of going to standby, and a fault needed a power cycle or a visit.