Skip to content
The CBII75 legacy is no longer supplied on new systems. Existing systems stay supported. For a new system, see the CBII75.

Overview

The CBII75 legacy is the first CBII75 (C-Battery Industrial Indoor): a 75 kWh battery rack with its own inverter. The current CBII75 has its own section: CBII75. Your EMS controls it over Modbus TCP with SunSpec models, but the control works its own way: one point starts and stops the rack, and the setpoint decides whether it runs. If you know SunSpec, read Where it differs from SunSpec first.

  • Start and stop the rack, and set its active power, charging or discharging.
  • Read the state of charge, the energy and the power limits.
  • See whether the inverter runs, stands by or is in fault, and reset a fault.
  • Reactive power or power factor control.
  • A total for the site: you address each rack on its own.
SunSpec CBII75 legacy
Start and stop 802_SetOp and 802_SetInvState 704_WSetEna: 1 runs, 0 stands by. The rack ignores 802_SetOp and 802_SetInvState
A setpoint of 0 Runs at 0 W Standby. Below 500 W either way counts as 0
802_WChaRteMax, 802_WDisChaRteMax The nameplate rate The limit right now
Off 701_InvSt = 0 The rack is running or in standby; your EMS never turns it off

Each model carries only the points in the Register reference.

Model SunSpec name You use it for
1 Common Identifying the rack and its software version
701 DER AC Measurement Delivered power and inverter state
704 DER AC Controls Starting, stopping and setting the power
713 DER Storage Capacity State of charge and energy
714 DER DC Measurement DC current and power
802 Battery Base Model Limits, battery voltage and fault reset

Models 702 and 715 are served as well, but you need nothing from them.