Overview
The CBII75 legacy is the first CBII75 (C-Battery Industrial Indoor): a 75 kWh battery rack with its own inverter. The current CBII75 has its own section: CBII75. Your EMS controls it over Modbus TCP with SunSpec models, but the control works its own way: one point starts and stops the rack, and the setpoint decides whether it runs. If you know SunSpec, read Where it differs from SunSpec first.
What your EMS can do
Section titled “What your EMS can do”- Start and stop the rack, and set its active power, charging or discharging.
- Read the state of charge, the energy and the power limits.
- See whether the inverter runs, stands by or is in fault, and reset a fault.
What it does not do
Section titled “What it does not do”- Reactive power or power factor control.
- A total for the site: you address each rack on its own.
Where it differs from SunSpec
Section titled “Where it differs from SunSpec”| SunSpec | CBII75 legacy | |
|---|---|---|
| Start and stop | 802_SetOp and 802_SetInvState |
704_WSetEna: 1 runs, 0 stands by. The rack ignores 802_SetOp and 802_SetInvState |
| A setpoint of 0 | Runs at 0 W | Standby. Below 500 W either way counts as 0 |
802_WChaRteMax, 802_WDisChaRteMax |
The nameplate rate | The limit right now |
| Off | 701_InvSt = 0 |
The rack is running or in standby; your EMS never turns it off |
Each model carries only the points in the Register reference.
SunSpec models
Section titled “SunSpec models”| Model | SunSpec name | You use it for |
|---|---|---|
| 1 | Common | Identifying the rack and its software version |
| 701 | DER AC Measurement | Delivered power and inverter state |
| 704 | DER AC Controls | Starting, stopping and setting the power |
| 713 | DER Storage Capacity | State of charge and energy |
| 714 | DER DC Measurement | DC current and power |
| 802 | Battery Base Model | Limits, battery voltage and fault reset |
Models 702 and 715 are served as well, but you need nothing from them.