A CBII75 (C-Battery Industrial Indoor) follows the EMS integration pages: the same points, addresses and start order, without 802_SetOp. It is a 75 kWh battery rack; its PCS is a stack of power modules. The first CBII75, with its own inverter, has its own section: CBII75 legacy. Not sure which one you have: contact support@c-battery.technology.

  • Write 802_SetInvState = 3 and 704_WSetEna = 1, then 704_WSet.
  • 802_SetOp is not used: the battery is always on the DC bus, and 802_SetOp reads 1.
  • The first start takes 8 to 15 s: the modules start in steps.
  • 704_WSet = 0 stops the modules. The next setpoint starts them again, which takes about 8 s each time.

802_SoC is net: use all of 0–100 %. At 0 % discharging stops and the discharge limits read 0; at 100 % charging stops.

701_W can differ from your setpoint, also while control is off:

  • When cell voltages are too low, the battery can charge by itself.
  • In a dangerous situation, it holds 0 W.
701_InvSt Meaning
0 Control is off: 704_WSetEna = 0 or 802_SetInvState is not 3
7 Control is on, 704_WSet is 0: the modules are stopped
3 Running
6 A module fault

802_AlmRst does nothing on a CBII75. For a fault that stays, contact support@c-battery.technology.