Overview
A CBII75 (C-Battery Industrial Indoor) follows the EMS integration pages: the same points, addresses and start order, without 802_SetOp. It is a 75 kWh battery rack; its PCS is a stack of power modules. The first CBII75, with its own inverter, has its own section: CBII75 legacy. Not sure which one you have: contact support@c-battery.technology.
Starting and stopping
Section titled “Starting and stopping”- Write
802_SetInvState= 3 and704_WSetEna= 1, then704_WSet. 802_SetOpis not used: the battery is always on the DC bus, and802_SetOpreads 1.- The first start takes 8 to 15 s: the modules start in steps.
704_WSet= 0 stops the modules. The next setpoint starts them again, which takes about 8 s each time.
State of charge
Section titled “State of charge”802_SoC is net: use all of 0–100 %. At 0 % discharging stops and the discharge limits read 0; at 100 % charging stops.
The battery protects itself
Section titled “The battery protects itself”701_W can differ from your setpoint, also while control is off:
- When cell voltages are too low, the battery can charge by itself.
- In a dangerous situation, it holds 0 W.
States and faults
Section titled “States and faults”701_InvSt |
Meaning |
|---|---|
| 0 | Control is off: 704_WSetEna = 0 or 802_SetInvState is not 3 |
| 7 | Control is on, 704_WSet is 0: the modules are stopped |
| 3 | Running |
| 6 | A module fault |
802_AlmRst does nothing on a CBII75. For a fault that stays, contact support@c-battery.technology.