The CBII75 legacy is no longer supplied on new systems. Existing systems stay supported. For a new system, see the CBII75.

Quickstart

These steps take one rack from standby to 7 kW discharge and back. For a first run, a Modbus tool is all you need. In your EMS, walk the SunSpec map instead of using these addresses: see the Register reference.

  1. Connect. Modbus TCP to the gateway’s IP address, port 502, Unit ID 100 + the rack’s number: 101 for rack 1. Registers 40000 and 40001 read SunS.
  2. Check it can run. 701_InvSt reads 3 (running) or 7 (standby). At 6 the rack is in fault: see Resetting a fault.
  3. Start. Write 704_WSetEna = 1. Once is enough: the rack keeps it.
  4. Set the power. Write 704_WSet = 70, both registers with function code 16. The register holds W / 100, so this is 7 kW discharge; −70 charges 7 kW.
  5. Check. 701_InvSt reads 3 and 701_W about 70.
  6. Stop. Write 704_WSet = 0. The rack goes to standby: 701_InvSt reads 7.
Step Point Address Value
1 SunS 40000–40001 read
2, 5 701_InvSt 40074 read
3 704_WSetEna 40299 1
4, 6 704_WSet 40301–40302 70, then 0
5 701_W 40080 read

With pymodbus 3.10 or later:

from pymodbus.client import ModbusTcpClient
UNIT = 101 # rack 1
client = ModbusTcpClient("192.0.2.100", port=502)
client.connect()
def read(address, count=1):
return client.read_holding_registers(address, count=count, device_id=UNIT).registers
def write(address, values):
client.write_registers(address, values, device_id=UNIT) # function code 16
def int32(value):
raw = value & 0xFFFFFFFF
return [raw >> 16, raw & 0xFFFF] # high word first
def int16(raw):
return raw - 0x10000 if raw >= 0x8000 else raw
assert read(40000, 2) == [0x5375, 0x6E53], "not a SunSpec device"
write(40299, [1]) # 704_WSetEna = 1
write(40301, int32(round(7000 / 100))) # 704_WSet: 7 kW discharge
inv_st = read(40074)[0] # 701_InvSt
watts = int16(read(40080)[0]) * 100 # 701_W, W_SF = 2
print(f"InvSt {inv_st}, {watts} W")
write(40301, int32(0)) # standby
client.close()