A CBEB3344 (C-Battery Energy Box) follows the EMS integration pages. On top of them it says whether it can run and why not, names every fault and who has to act, and keeps a heartbeat both ways. Its own points are in the Register reference.

  • 802_WChaRteMax and 802_WDisChaRteMax are the nameplate rate: fixed for the installation.
  • 802_SoC is net: use all of 0–100 %. At 0 % discharging stops, at 100 % charging; 802_State then reads 5.
802_State Name Meaning
1 DISCONNECTED Off the DC bus: write 802_SetOp = 1
3 CONNECTED Dispatch it
5 SOC PROTECTION At a state of charge limit
99 FAULT It cannot run

713_Sta adds warnings: 0 OK, 1 WARNING (it keeps running), 2 ERROR.

At 99, stop asking for power and show your operator 701_MnAlrmInfo: the active faults and warnings in words. The battery resumes by itself once the fault is gone, unless someone has to act:

  • 802_AlmRst = 1 resets the PCS’s own faults once their cause is gone, for example after a grid outage.
  • 802_EvtVnd1 bit 9: physical intervention required, someone has to go to the battery. Do not write 802_AlmRst while it is set. Safety trips are never reset remotely.

Every bit, and who acts: Fault reference.

Point Whose Behaviour
715_DERHb Ours +1 every second while it can run. No change for 5 s: treat the battery as gone
715_ControllerHb Yours +1 every second, both registers in one write. Where the check is on, 10 s without a change holds the battery at 0 W

One fault does not stop ours: EMS heartbeat lost. You may wait for ours to move before you start counting yours. Write yours on every site, whether the check is on there or not.