Skip to content

Reactive power

A CBEB1045 can inject or absorb reactive power while it discharges. You ask for it in one of two ways: a reactive power setpoint in var, or a power factor. Both are standard SunSpec points in model 704.

  • Reactive power applies while 704_WSet is above 0 and the battery is running.
  • While it charges, or is stopped, it runs without reactive power. Your setpoint stays stored and applies again at the next discharge.
  1. Write 704_VarSet in var. Positive injects reactive power (over-excited: the grid voltage rises), negative absorbs it (under-excited: the grid voltage drops).
  2. Write 704_VarSetEna = 1.

Write 704_VarSetEna = 0 to end it. Leave 704_VarSetMod at 4: the setpoint is in var.

  1. Write 704_PFWInj.PF, from 0.8 to 1.0. A lower value counts as 0.8.
  2. Write 704_PFWInj.Ext: 0 injects reactive power (over-excited), 1 absorbs it (under-excited).
  3. Write 704_PFWInjEna = 1.

Write 704_PFWInjEna = 0 to end it.

Switch on one of the two. With both on, the power factor applies.

  • 702_VarMaxInjRtg and 702_VarMaxAbsRtg are the most it can inject or absorb with every module running. At low power fewer modules run, and it caps your setpoint to what those can deliver.
  • Reactive power has priority. When active and reactive power together are more than the modules can carry, it lowers the active power: 701_W can be lower than 704_WSet.
  • A new setpoint is not immediate.

Check reactive power on your grid meter. 701_Var, 701_VA and 701_PF are calculated by the modules, not measured: 701_Var reads above 0 without any setpoint, and it has no direction of its own.

Addresses count from 0, as in the register reference. Find them by walking the SunSpec map.

Point SunSpec name Address Type Unit Access Notes
704_VarSetEna Set Reactive Power Enable 40312 enum16 – read/write 0 off, 1 on
704_VarSetMod Set Reactive Power Mode 40313 enum16 – read/write 4: the setpoint is in var
704_VarSet Reactive Power Setpoint (Vars) 40315–40316 int32 var read/write Positive injects, negative absorbs
704_VarSet_SF Reactive Power Scale Factor 40334 sunssf – read
704_PFWInjEna Power Factor Enable (W Inj) 40279 enum16 – read/write 0 off, 1 on
704_PFWInj.PF Power Factor (W Inj) 40336 uint16 register × 0.001 read/write 800 to 1000
704_PFWInj.Ext Power Factor Excitation (W Inj) 40337 enum16 – read/write 0 over-excited, 1 under-excited
704_PF_SF Power Factor Scale Factor 40330 sunssf – read
702_VarMaxInjRtg Reactive Power Injected Rating 40233 uint16 var: register × 100 read
702_VarMaxAbsRtg Reactive Power Absorbed Rating 40234 uint16 var: register × 100 read
702_Var_SF Reactive Power Scale Factor 40273 sunssf – read