Reactive power
A CBEB1045 can inject or absorb reactive power while it discharges. You ask for it in one of two ways: a reactive power setpoint in var, or a power factor. Both are standard SunSpec points in model 704.
Only while discharging
Section titled “Only while discharging”- Reactive power applies while
704_WSetis above 0 and the battery is running. - While it charges, or is stopped, it runs without reactive power. Your setpoint stays stored and applies again at the next discharge.
A reactive power setpoint
Section titled “A reactive power setpoint”- Write
704_VarSetin var. Positive injects reactive power (over-excited: the grid voltage rises), negative absorbs it (under-excited: the grid voltage drops). - Write
704_VarSetEna= 1.
Write 704_VarSetEna = 0 to end it. Leave 704_VarSetMod at 4: the setpoint is in var.
A power factor
Section titled “A power factor”- Write
704_PFWInj.PF, from 0.8 to 1.0. A lower value counts as 0.8. - Write
704_PFWInj.Ext: 0 injects reactive power (over-excited), 1 absorbs it (under-excited). - Write
704_PFWInjEna= 1.
Write 704_PFWInjEna = 0 to end it.
Switch on one of the two. With both on, the power factor applies.
Limits
Section titled “Limits”702_VarMaxInjRtgand702_VarMaxAbsRtgare the most it can inject or absorb with every module running. At low power fewer modules run, and it caps your setpoint to what those can deliver.- Reactive power has priority. When active and reactive power together are more than the modules can carry, it lowers the active power:
701_Wcan be lower than704_WSet. - A new setpoint is not immediate.
Checking it
Section titled “Checking it”Check reactive power on your grid meter. 701_Var, 701_VA and 701_PF are calculated by the modules, not measured: 701_Var reads above 0 without any setpoint, and it has no direction of its own.
Points
Section titled “Points”Addresses count from 0, as in the register reference. Find them by walking the SunSpec map.
| Point | SunSpec name | Address | Type | Unit | Access | Notes |
|---|---|---|---|---|---|---|
704_VarSetEna |
Set Reactive Power Enable | 40312 | enum16 | – | read/write | 0 off, 1 on |
704_VarSetMod |
Set Reactive Power Mode | 40313 | enum16 | – | read/write | 4: the setpoint is in var |
704_VarSet |
Reactive Power Setpoint (Vars) | 40315–40316 | int32 | var | read/write | Positive injects, negative absorbs |
704_VarSet_SF |
Reactive Power Scale Factor | 40334 | sunssf | – | read | |
704_PFWInjEna |
Power Factor Enable (W Inj) | 40279 | enum16 | – | read/write | 0 off, 1 on |
704_PFWInj.PF |
Power Factor (W Inj) | 40336 | uint16 | register × 0.001 | read/write | 800 to 1000 |
704_PFWInj.Ext |
Power Factor Excitation (W Inj) | 40337 | enum16 | – | read/write | 0 over-excited, 1 under-excited |
704_PF_SF |
Power Factor Scale Factor | 40330 | sunssf | – | read | |
702_VarMaxInjRtg |
Reactive Power Injected Rating | 40233 | uint16 | var: register × 100 | read | |
702_VarMaxAbsRtg |
Reactive Power Absorbed Rating | 40234 | uint16 | var: register × 100 | read | |
702_Var_SF |
Reactive Power Scale Factor | 40273 | sunssf | – | read |